How to Verify the Accuracy of a Clamp Meter without using a Standard Coil?

with No Comments

In my last post, I presented how to calibrate a clamp meter using a Fluke 5500 standard coil to amplify a current simulated from the Fluke 5522a. You can attain the required current output by using the standard coil.

A Clamp meter is used by clamping it on a current carrying conductor in order to check the current without breaking or opening a cable.

In this post, I will show how to verify a clamp meter without using a Fluke 5500 standard coil (which is the required standard for calibration). You will also discover here how to properly set up and measure a cable using the clamp meter.  We will only focus here on the current function of the clamp meter which is its basic application. Ok, let us start by following the figures below.

Verifying a Clamp Meter zero reading

I will use a single line of cable ( a connector) to demonstrate the verification process. We will still need the Multiproduct calibrator as our source of current (dc).

If you have other instruments or calibrator that generates current with a known value, like a calibrated power supply, it will also do.

Based on figure 1 below, notice that Fluke 5522a is generating a current but the reading is zero (0), why?

Zero reading means there is no current flowing in the conductor. But in a clamp meter, this is not always the case. A zero reading can also happen if you measure a conductor simultaneously that is out of phase, meaning the direction of the current is different, one is going down while the other is going up. Notice that the red and black cable has the opposite direction of current flow, so the net current becomes zero.

The lesson here is to measure a conductor only in the same direction of flow or polarity. We need to separate the two wires and measure only a single wire in order to attain a single direction of current flow.

Figure 1.

Clamping a cable with opposite or out of phase current flow simultaneously
Clamping a cable with opposite or out of phase current flow simultaneously

Verification of Current From a Single Conductor.

Now, based on figure 2 and 3, I separated the red wire and clamped only the black wire. Then simulated current of 1 A and 2 A.  As you notice, it is already having a reading. The standard simulated current reading from Fluke 5522a is compared to the reading of the clamp meter.

As you also observe, one piece of wire will only read exactly the value of the simulated current, a1:1 ratio. But by using a multiple piece or coil of wires, we can increase the value of the current without increasing the current value itself.

See figure 4 for this presentation.

Figure 2.

Clamping just a single cable will result to a current reading.
Clamping just a single cable will display a current reading.

Figure 3.

1:1 ratio of current to cable turns
1:1 ratio of current to cable turns

Verification of Current from a Multiple Conductor.

If you have a limited current source but you like to increase the value of current to be verified and measured, what you can do is to increase the number of coils, turns, or windings where the clamp meter will be clamped-on.

Based on the figure below, notice that I increase the number of windings in the black wire, (becomes 2 coils). Observe that I have a current of 2 A  but the clamp meter displays a current of 4 A. The Ratio of the current to wire becomes 1:2. Any current value will be amplified by a factor of 2.

You can increase more the value of the current by increasing the number of turns in the conductor. This is the principle of the Fluke 5500 standard coil where it has a 50 turns coil. Any current that passes through that coil will be multiplied by a factor of 50. It has a ratio of 1:50.

Figure 4.

Clamping to a two turns wire that resulted in a doubled output. A 2A input resulted to a 4A output being displayed by the clamp meter.
Clamping to a two turns wire that resulted in a doubled output. A 2A input resulted in a 4A output being displayed by the clamp meter.

Conclusion

This is how we can verify the accuracy of a clamp meter without a standard coil.  You can use this set up if you do not have a standard coil. I have shown you how a number of turns of wire can amplify a current value. The wire I use here is limited in length but in order to have a more accurate reading, make sure that the conductor that is coiled or being clamped-on is in the middle of the clamp meter jaw.

For more details on how to calibrate a clamp meter, you may visit my other post here.

Thank you for visiting my site, please comment and subscribe.

Edwin

Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.