Megger Insulation Tester Calibration Procedure

with 12 Comments

 

Megger with Resistance box and Precision Multimeter as the Reference Standard
Megger with Resistance box and Precision Multimeter as the Reference Standard

Have you ever wonder why the cables on your appliances are safe to hold while plugging it into the electrical source? Or the electrical lines going into your house does not shock you everytime you touch a metal post or every time it is wet? It is because the conductors are properly insulated. But any leak or shortage in these electrical wires can cause shock or damage to appliances.

That is why every unit or appliances, building electrical connections or electric motors need to be tested first before they are released for public use. This is where an insulation tester is being used.

Insulation testers are used to check and detect if there is a leak of current in a conductor or other electrical components. And the most commonly used Insulation tester is the Megger Tester (a brand and a company name). 

For most people, once you say Megger, it is automatically an insulation tester. But we should also know that Fluke has its own Insulator Tester which is the Fluke 1507 insulation tester.

In this article, I will share how to check and verify the accuracy of your megger tester in measuring a resistance value that you may implement before using your Megger. Also, it includes the verification of the output voltage to ensure that you have a reliable reading.

I will also present a calibration procedure that you can implement for your in-house calibration just in case you have the necessary reference standards which I will present it here. In this post, I will be using the Megger BM11D.

What is an Insulation Tester?

A multimeter is used as insulation tester but in a limited and mostly a continuity test only. But for detecting and testing for a leakage current during a normal or overloaded condition, a special instrument known as the Insulation tester is used.

When we are using a multimeter, we are measuring a resistance, voltage, and current.  Based on this, I hope we are familiar with the term Insulation. This means that a current cannot pass or leak through a certain conducting wire when it is properly insulated or protected. These wires may be inside a building, appliances or an electric motor.

Functions of an Insulation tester: Principles of Operation

  •    The main function is to test the insulation of a set of conducting wires by measuring the resistance. The higher the resistance reading, the better. Usually in Mega Ohms reading. A lower value of resistance means that there is a short or leakage of current causing the resistance to drop.
  •    Used as a voltage source to test for the integrity of the conductor. An insulation tester has the capability to source out or generates a high amount of voltage. This voltage is injected into conducting wires to test if the insulation can withstand the high voltage. An insulated conductor can have a normal reading in a low voltage value but during exposure to a high voltage,  the insulation can break and a leakage may occur.
  •    Function as a continuity tester. Testing for continuity on a very long cable of wire cannot be guaranteed by a simple multimeter. Because of the high voltage generated by the insulation tester, you can measure a significant amount of resistance.
  • High resistance (infinity) reading means open while a zero or very low resistance means shorted.  But no need to record because most Insulation tester has an audible alarm for short or open status.

How to use and verify the accuracy of a Megger tester 

Since we already know the operating principles of an insulation tester, I will show you how to verify the accuracy of your Megger Insulation Tester by using a resistor and a multimeter.

Resistance Function verification

Resistance Verification
1. Check first the actual resistance of the resistor by using a precision multimeter 2. Then connect to Megger to see and compare its reading.

Just directly measure a resistor with a known value. Please see the figure below. If you want to record a highly accurate result, measure first the resistor using the multimeter in order to get its actual value.

  1. Set the required voltage to be generated in the resistor ( 500 V)
  2. Connect the resistor to its probe.
  3. Then Press TEST button.

Voltage Function Verification

  1. Remove the resistor and transfer the probes on the port of the multimeter
  2. Set the multimeter on the required range ( Vdc)
  3. Set the Megger on the desired voltage range.
  4. Push the TEST button of the Megger to generate the set 

Readings should be within the specifications provided by the manufacturer.

Megger insulation Tester calibration procedure 

Megger Insulation Tester is measuring a resistance by generating a voltage. Using Ohms Law (V=IR), we can compute the value of the resistance. Because of this, we cannot use a direct simulation of signal like for example from a process calibrator. The process calibrator is also generating a voltage that has an effect on the measured value.

In this procedure, we will be using the Resistance Box to provide an analog resistance for the Megger. A Decade resistance box is a set of resistors arrange in such a way to provide a combined resistance reading in a decade interval packed inside a box. (Megger has its own which is called a megger calibration box)

Another reference standard is the Fluke multimeter, we need a high range and resolution multimeter capable of reading the entire range of your Megger. If you cannot reach the entire range, you can still calibrate but with a limited range that is approved by the user.

         Calibration Method:

This is accomplished by comparing the resistance output of the decade box to the display of the Megger.  And also the voltage display in the Megger to the voltage reading of the multimeter. This procedure can be used on all Insulation Tester that accepts an analog resistance.

Requirements:

  • Warm-up time (UUC): At least 1 hour for proper stabilization
    Decade Resistance Box and connecting leads
    Decade Resistance Box and connecting wires
  • Temperature:   23 +/- 5 deg C
  • Humidity:         50 +/- 30%
  • Measurement Data Sheet (MDS) or a Megger Test Report (check this link to learn more about Measurement Data Sheet)

Reference standard to use:

  1. Decade Resistance Box ( Calibration Box)
  2. Fluke  Precision Multimeter 8846A
  3. Thermohygrometer ( to monitor Temperature and Humidity)
  4. Connecting wires

Calibration procedure:

  1. High voltage is generated in this procedure, always observe safety.
  2. Check the Megger Tester for any visual defects that can affect its accuracy. Discontinue calibration if any defect is noted.
  3. Clean the Megger Tester with soft cloth Check if it has good batteries, replace low powered batteries.
  4. Power on the unit and allow stabilization of 1 hour, to be conditioned on the environmental conditions of the room.
  5. Prepare the measurement data sheet (MDS) and record all necessary details or information (Brand, Model, serial #, etc).
  6. Determine the test points to be calibrated on the Megger Tester, choose at least 5 test point covering the whole range or as per user range. Record this on the MDS.
  7. Using Fluke Precision Multimeter, connect the necessary test leads to measure DC Voltage
Megger Voltage Verification Setup
Megger Voltage Verification Setup

DC Voltage Verification:

    1. Connect positive terminal of the Megger to the positive  Input HI of the Fluke multimeter and the negative terminal to the LO Return side.
    2. Set the Megger (Unit Under Calibration) to DC Voltage mode. Select the range of voltage to be generated.
    3. Press the TEST button to generate each of the required voltage setpoint values.
    4. Take note of the measured value on the multimeter.
    5. Wait for the display to stabilize then get the reading. Record readings on the MDS or Megger Test report.
    6. Take at least 3 trials for each set point
    7. Repeat number 2 to 6 until all ranges are covered.

     Resistance Verification:

  1. Remove the connection probes of the Megger that is connected on the multimeter.
  2. Now connect the probes to the terminal of the Decade resistance box ( same connections as with the multimeter).
  3. Set the resistance value of the decade resistance box to the desired value by turning the knobs. ( example is 100 Mohm)
  4. Press the TEST button, the Megger will inject a voltage to the resistor and generate the required resistance value.
  5. Wait for the display on the Megger to stabilize then get the reading. Record readings on the MDS.
  6. If the readings are already within limits, update the corresponding record, do labeling and sealing and issue to the owner, otherwise, do necessary repair or adjustment.

 8, End of procedure

Based on manufacturers Specifications, below are the tolerance limits that can be used.

Voltage reading

±5% of nominal test voltages (load resistance >100 MΩ)

Resistance Reading

±5% 1 MΩ to 100 GΩ at 5 kV

±5% 1 MΩ to 10 GΩ at 500 V

±20% outside these limits (above 100 kΩ)

Example:

Voltage output is 500 Vdc,  allowable limits is (0.05×500 = 25 V)

Therefore, tolerance value is from +/- 25 of 500 or (475 to 525) Vdc

Want to learn how to interpret a calibration certificate properly? Visit my other post, click here.

Conclusion

Understanding Resistance measurements have so many ways and Megger Insulation Tester is one of the instruments that may confuse you or intrigue you if you are new in electrical measurement.  IN order to be clear in this matter,  I have provided a simple explanation on the principle of its measurement. We have known that it is using an analog signal in order to generate the required resistance.

Once you have understood this principle, it is now simple to calibrate or verify an insulation tester. I have presented in this post on how to verify before use and calibrate a Megger Insulation Tester by using a reference standard.

Looking for an INSULATION TESTER, Check this page insulation tester.

 

Thanks for visiting my site, please leave a comment and subscribe.

Edwin

 

 

 

12 Responses

  1. Rohan Perera
    | Reply

    Very informative

    Thank you

    • edsponce
      | Reply

      Hi Sir,
      Your Welcome. I Appreciate you liked it.

      Best Regards

  2. Frank Lampard
    | Reply

    Useful article sharing blog for insulation tester. Important and informative idea sharing this blog. Guys would love it.

    • edsponce
      | Reply

      Thank you sir, appreciate your comment.

      Best regards,
      Edwin

  3. Fernando
    | Reply

    Just come across with your website and i find it very informative and also it gives me an idea in the calibration of other instruments. I would like to know if calibrating an analogue insulation tester like model specifically Megger BM12 would require a resistance load to be connected across the measuring DVM if you intend to measure the output DC voltage of the Megger BM12?
    On the other matter, there are insulation tester like Fluke 150X Series, wherein in the Source Voltage is verified or measured using a Resistance Load (or applied load) of 1 MΩ, 500kΩ, 250kΩ, 100kΩ, and 50 kΩ for tester (DUT) range of 1000 V, 500 V, 250 V, 100 V and 50 V respectively. This was taken for the Fluke 150X Series calibration Manual in the verification test under “Source Voltage Accuracy Test, R- Nominal. Do we require load resistance to be connected to the DVM when checking or verifying the insulation tester output voltage? Does this apply to all the insulation tester of various model? Thank you so much for your attention on this matter.

    • edsponce
      | Reply

      Hi Fernando, I am happy to hear that you have learned from my post.

      About your query if it requires a resistance load to be connected across the DVM to measure its DC voltage output, the answer is it can be but no need, the BM12 will source out a voltage that can be directly read by a multimeter or DVM. You only need a resistance load if you want to get the current generated by the Megger where in a series connection with the DVM is applied.

      Also, Resistance load are used as a verification standard to check if the resistance measured or displayed by the Megger or insulation tester is accurate or within acceptable range as I present it in the post. All insulation tester I believe are applicable in this principle because its purpose is to measure the insulation (a high resistance value which is an analog type).

      I hope I have answered your query. Please do not hesitate to comment further.

      Best Regards,
      Edwin

  4. Cheslyn
    | Reply

    Thanks this makes life so much easier

    • edsponce
      | Reply

      H Cheslyn, you’re welcome and Thank you also.

      Best Regards,
      Edwin

  5. Chris Casao
    | Reply

    Salamat kabayan. Malaking tulong to sa aking baguhan sa calibration.

    • edsponce
      | Reply

      Walang anuman Kabayan, Salamat sa pag bisita sa aking site. Kung may katanungan mag message lang po.
      Maraming salamat.

      Edwin

  6. Vijay Rawat
    | Reply

    Sir,
    One of the best description I have to read or understand.
    Really great ful to you sir.

    • edsponce
      | Reply

      Hi Mr. Vijay,
      I am happy to know and appreciate your comment. Please let me know other things that I can help you with about calibration.

      Best Regards,
      Edwin

Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.